Permit: T03ME00526

Parcel: 110151170


Addresses:

5502 E GLENN ST #A


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03ME00526

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ OK FOR C OF O.
10/13/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ UNIT A DRYER VENT ELBOW NOT CONNECTED TO DRYER VENT PIPE AT BOTTOM. RECALL FOR INSPECTION - WHAT PART DON'T YOU UNDERSTAND ABOUT ROUNDING THE CORNERS OF THE SQUARE DRYER VENTS? THIS IS THE LAST BLDG I WILL ACCEPT THIS IN.
10/07/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ ALL UNITS (DRYER VENTS) - WHEN ATTACHING A ROUND PIPE INTO A SQUARE PIPE, YOU MUST ROUND OFF THE CORNERS OF THE SQUARE PART AND SEAL BETTER THAN YOU HAVE BEEN. UNIT 'C' HAS NO TAPE AT ALL. UNIT 'C' PROVIDE SCREWS WHERE FURNACE VENT CONNECTOR CONNECTS TO DOUBLE WALL VENT. UNIT A AND D DRYER VENTS ARE LOOSE. SECURE AS NEEDED. UNIT D - WATER HEATER VENT IS UPSIDE DOWN IN CLOSET AND NOT CONNECTED IN THE ATTIC. RECALL FOR INSPECTION.