Permit: T03ME00520

Parcel: 13632003F

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/17/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ CORRECTIONS HAVE BEEN MADE.
09/23/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/1) PROVIDE A TRAP ON CONDENSATE DRAIN LINE. 2) PROVIDE CLEARANCE WHERE REFER LINE INSULATION IS TOUCHING VENT CONNECTOR. 3) 3/8" I.D. GAS FLEX CONNECTOR NOT ADEQUATE FOR 100,000 BTU. SEE LISTING ON GAS FLEX. RECALL FOR INSPECTION.