Permit: T03ME00518

Parcel: 136345560


Addresses:

3630 S CHESIN DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/07/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE
09/25/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 3/8" I.D. GAS FLEX CONNECTOR NOT ADEQUATE FOR 103,500 BTU FURNACE. CHANGE FLEX TO 1/2" I.D. OR PROVIDE THE LISTING ON THE FLEX USED THAT SHOWS OTHERWISE. EVERYTHING ELSE IS OK. RECALL FOR INSPECTION.