Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/17/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE. |
| 09/15/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE A TRAP ON CONDENSATE DRAIN. 2) CONDENSOR OVERFUSED. 50 AMP IS MAX FUSE SIZE. LABEL CIRCUIT BREAKER INSIDE PANEL. SECURE ELEC. CONDUIT INDEPENDENTLY. DO NOT SECURE TO EXISTING CONDUIT WITH WIRE. RECALL FOR INSPECTION. |