Permit: T03ME00474

Parcel: 135061400

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/23/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ALL CORRECTIONS HAVE BEEN MADE.
09/05/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) LABEL OR IDENTIFY CIRCUIT BREAKER FOR CONDENSOR 2) VENT ON CONDENSATE DRAIN TRAP MUST BE DOWNSTREAM OF TRAP. VENT IS NOT REQUIRED FOR THIS APPLICATION. 3) CONDENSOR IS OVERFUSED AT 50 AMP. 45 AMP IS MAXIMUM FUSE SIZE 4) DO NOT EXTEND 3/8 DRAIN LINE INTO THE SEWER VENT. TERMINATE OVER THE TOP WITH AN AIR GAP. STRAP 3/8 LINE TO VENT. 5) JOINTS ON REFER LINE INSULATED COMING APART ON ROOF. FLUE OR TAPE JOINTS. PROVIDE A BLOCK AND CLAMP ON REFER LINES