Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/14/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) ELECT. HIGH VOLTAGE - INCORRECT FUSE SIZE, FUSE TOO BIG.. REVERSE SWITCH, LESS THAN 30" IN FRONT. 2) CONTROL WIRING EXPOSED TO SUN, NO FLASHING AT ROOF PENETRATION. 3) GAS LINE INCOMPLETE. 4) CONDENSATE PIPING CAN'T DUMP OFF EDGE OF ROOF. PVC MUST BE PAINTED. IMPROPER TERMINATION. 5) DUCT FLEX CONNECTORS, RAIN SHIELD, BLOCKING COVER ACCESS TO FILTER TRACK. NOTE!! DO NOT RECALL FOR INSPECTION UNTILL EACH OF THESE ITEMS HAS BEEN CORRECTED. |