Permit: T03ME00438

Parcel: 11446208A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03ME00438

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE.
08/04/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PERMANENTLY LABEL EQUIPMENT ON ROOF W/SUITE NUMBER. 2) MARK UNIT DATA PLATES W/ PROPER HEAT STRIP INSTALLED AND FUSE UNIT ACCORDINGLY. 3) EXTEND CONDENSATE DRAIN PIPE ALL THE WAY TO ROOF SCUPPER. PAINT EXPOSED PVC WITH LATEX PAINT. 4) PROVIDE OUTSIDE AIR INTAKES ON A/C UNITS. 5) #10 WIRE NOT ADEQUATE FOR 60AMP. CIRCUIT FROM DISCONNECT TO A/C UNIT. ELECTRICAL ON ROOF HAS AN OPEN COVER ON LB. #10 WIRE NOT ADEQUATE FOR 50 AMP. CIRCUIT ON CONDENSOR ON ROOF. COMBUSTION AIR HOOD NOT CONNECTED ON ROOF. ELEC. CONDUIT NOT CONNECTED. 6) PROVIDE A CAP ON UNUSED GAS LINE IN FURNACE CLOSET.