Permit: T03ME00428

Parcel: 11006180A


Addresses:

2850 N EASTGATE DR

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/11/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/1) PROVIDE A TRAP ON CONDENSATE DRAIN. 2) UNIT OVERFUSED AT 30 AMP. 25 IS MAX. RE-CALL FOR FINAL. YOUR CONTRACTOR DID A NICE JOB.