Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03ME00404
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2009 | MECHANICAL - FINAL | Approved | ||
09/25/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/1) CONDENSATE DRAINS CANNOT BE DIRECTLY CONNECTED TO A SEWER VENT. THIS CODE CHANGED 3 YEARS AGO. 2) ANY SEWER VENTS WITHIN 10' OF A FRESH AIR INTAKE MUST BE 10' AWAY OR 2' HIGHER THAN INTAKE OPENING. | |
09/22/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/1) CONDENSATE CAN NO LONGER TERMINATE INTO A SEWER VENT WITHOUT PROPER FITTINGS. CALL ME TO DISCUSS ALTERNATE METHOD. 909-4712 - JIM. 2) PERMANENTLY LABEL EQUIPEMENT WITH SUITE NUMBER. ALSO PROVIDE A PERMIT FOR THE UNIT INSTALLED LAST YEAR. |