Permit: T03ME00399

Parcel: 135111170


Addresses:

7602 E 35TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/01/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE
07/25/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) USE A CHASE NIPPLE WHERE ELEC. WIRES ENTER THE CABINET OF A/C UNIT. 2) DISCHARGE LINE FROM A CONDENSATE PUMP CAN DRAIN INTO A SEWER VENT, BUT THE DRAIN LINE CANNOT EXTEND INTO THE SEWER VENT. TERMINATE WITH A 1 DEGREE AIR JAYS(?) BETWEEN THE TOP OF THE VENT AND THE END OF DISCHARGE LINE. RE-CALL FOR INSPECTION.