Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/01/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE |
| 07/25/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) USE A CHASE NIPPLE WHERE ELEC. WIRES ENTER THE CABINET OF A/C UNIT. 2) DISCHARGE LINE FROM A CONDENSATE PUMP CAN DRAIN INTO A SEWER VENT, BUT THE DRAIN LINE CANNOT EXTEND INTO THE SEWER VENT. TERMINATE WITH A 1 DEGREE AIR JAYS(?) BETWEEN THE TOP OF THE VENT AND THE END OF DISCHARGE LINE. RE-CALL FOR INSPECTION. |