Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/25/2003 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/08/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0935*/ A/C UNIT STILL OVERFUSED. CONTROL WIRING STILL EXPOSED TO SUNLIGHT. ELEC. DISCONNECT STILL NOT SECURED. BLOCK AND CLAMP ELEC. CONDUIT ON ROOF. PAINT EXPOSED PVC W/LATEX PAINT. PAY A RE-INSPECTION FEE PRIOR TO NEXT INSPECTION. RE-CALL FOR FINAL. |
| 07/25/2003 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) A/C UNIT OVERFUSED. 35 AMP IS MAX FUSE SIZE, NOT 60 AMP. 2) CONDENSATE TERMINATION NOT TO CODE. HAVE YOUR CONTRACTOR CALL ME AT 791-5550 EXT 1146, BETWEEN 7:15 AM AND 7:45 AM TO DISCUSS ALTERNATE METHOD. 3) CONTROL WIRING MUST BE SUN RESISTANT OR USE CONDUIT. 4) BLOCK AND CLAMP GAS PIPE. 5) SECURE ELEC. DICONNECT. RE-CALL FOR INSPECTION. |