Permit: T03ME00363

Parcel: 121110660

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/03/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
10/28/2003 MECHANICAL - FINAL Cancelled IVRS - Ri canceled
09/17/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ UNITS ARE OVERFUSED AT 125 AMP. 90 AMP IS MAX FUSE SIZE. RECALL FOR INSPECTION.
07/07/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1) 3/8" I D GAS FLEX CONNECTOR NOT ADEQUATE FOR 250,000 BTU. SEE LISTING ON GAS FLEX & SIZE ACCORDINGLY. 2)#6 WIRE NOT ADEQUATE FOR 90 AMP CIRCUIT FROM ELEC DISCONNECT TO A/C EQUIPMENT. 3) PROVIDE CLAMPS ON GAS PIPE & CONDENSATE DRAIN. 4) NEED ACCESS TO CIRCUIT BREAKERS. RECALL FOR INSPECTION WHEN SOMEONE WILL BE HERE TO PROVIDE ACCESS.