Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/03/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/28/2003 |
MECHANICAL - FINAL |
|
Cancelled |
IVRS - Ri canceled |
| 09/17/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ UNITS ARE OVERFUSED AT 125 AMP. 90 AMP IS MAX FUSE SIZE. RECALL FOR INSPECTION. |
| 07/07/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1) 3/8" I D GAS FLEX CONNECTOR NOT ADEQUATE FOR 250,000 BTU. SEE LISTING ON GAS FLEX & SIZE ACCORDINGLY. 2)#6 WIRE NOT ADEQUATE FOR 90 AMP CIRCUIT FROM ELEC DISCONNECT TO A/C EQUIPMENT. 3) PROVIDE CLAMPS ON GAS PIPE & CONDENSATE DRAIN. 4) NEED ACCESS TO CIRCUIT BREAKERS. RECALL FOR INSPECTION WHEN SOMEONE WILL BE HERE TO PROVIDE ACCESS. |