Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/07/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/03/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/02/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MINIMUM AMPS 21.6 UNIT FUSED AT 20 AMPS MUST BE 25 OR 30 AMP FUSES, 60 M HEAT, 30,000 BTUH COOL 2) BLOCK/CLAMP RIDGED 1/2" GAS LINE PROPERLY 3) CONDENSATE DRAIN-NOT RUN 4) BLOCK, CLAMP ELECTRIC HIGH VOLTAGE EMT. |