Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE |
| 06/24/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
1)RECONNECT THE GAS LINE BACK TO THE SHUT OFF VALVE IN THE CLOSET, THEN TEST THE NEW GAS PIPE. 2) VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF THE TRAP. 3)HOMEOWNER IS TAKING CARE OF ELEC. CORRECTION & SEWER VENT CORRECTION. RECALL FOR INSPECTION. |
| 06/23/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) EVAP COOLER CANNOT BE POWERED FROM THE SAME FUSE BANK AS THE A/C UNIT. YOU CAN USE THE AIR CONDITIONER CIRCUIT IF YOU FUSE THE EVAP COOLER SEPERATELY 2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. REPLACE DAMAGED PIECE OF VENT PIPE. PROVIDE MINIMUM 1/8" PER FT. SLOPE 3) PROVIDE A PRESSURE TEST ON NEW GAS PIPE. RECALL FOR INSPECTION |