Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/21/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/14/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE A ROOF JACK WHERE ELEC. CONDUIT PENETRATES THE ROOF. 2) YOU CAN NOT USE A CHASE NIPPLE TO CONNECT TO A CIRCUIT PANEL. USE A CLOSE NIPPLE W/ LOCK NUTS. PROVIDE A BOND BUSHING IF USING REDUCING WASHERS AT KNOCK OUT TO CREATE AN ADEQUATE BOND WITH PANEL. SEE SECTION 110-3, ARTICLE 250, 1999 NEC. LABEL CIRCUIT BREAKER. 3) TERMINATE CONDENSATE DRAIN LINE WITH A 1" AIR GAP OVER SEWER PIPE. DO NOT RUN THE DRAIN LINE INTO THE VENT PIPE. |