Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ALL CORRECTIONS HAVE BEEN MADE |
| 06/11/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CONDENSATE CANNOT TERMINATE INTO A HOLE DRILLED INTO THE SIDE OF A SEWER WASTE VENT. IF PLUMBING THE WATER, TERMINATE OVERT THE TOP OF THE VENT WITH AN AIR GAP 2) IDENTIFY THE CIRCUIT BREAKER FOR CONDENSING UNIT, RECALL FOR INSPECTION |