Permit: T03ME00232

Parcel: 11010121A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/19/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ALL CORRECTIONS HAVE BEEN MADE.
06/13/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/#8 WIRE FROM ELECT DISCONNECT TO A/C UNIT NOT ADEQUATE FOR 60 AMP. USE #6 WIRE OR SMALLER FUSES.
#2 DO NOT EXTEND CONDENSATE DRAIN INTO THE SEWER VENT. TERMINATE OVER THE 90 "ELL WITH A 1" AIR GAP. RECALL FOR INSPECTION.
06/05/2003 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) UNIT NOT READY FOR INSPECTION YET. JOB'S WILL RECALL WHEN READY