Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/09/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/06/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*30,000 BTUH COOL. 50,000 BTU HT. IMPROPER CONDENSATE TERMINATION. 1.) CAN'T DUMP OVER SIDE OF FACIA CONTINUE TO GRD. OR GUTTER, W/DOWN SPOUT, BOTH UNITS. 2.) PVC NEEDS TO BE PAINTED W/LAYTEX PAINT. 3.) EAST UNIT MAX FUSE SIZE 30 UNIT FUSE AT 60 AMPS. |