Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03ME00159
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/17/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE AN OVERFLOW SENSOR ON EVAP. COIL 2. EXTEND FURNACE VENT 3' ABOVE COMBUSTION AIR INTAKE 3. DO NOT USE COLD WATER PVC ON WATER HEATER T&P DRAIN LINE. 4. USE COPPER OR CPVC |