Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03ME00153
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*/ 1) ALL CORRECTIONS HAVE BEEN MADE 2) 25 PSI TEST IS OK 3) OK TO CONNECT TO FURNACE | |
| 10/31/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*/ 1) GAS LINE NOT HOLDING PRESSURE 2) SEAL TITE FITTING STILL LOOSE A CONNECTION TO A/C UNIT. RECALL FOR INSPECTION | |
| 06/24/2003 | MECHANICAL - FINAL | Denied | 1) #10 ELEC. WIRE NOT ADEQUATE FOR 50 AMP CIRCUIT. #10 ONLY GOOD UP TO 30 AMP. USE #8 WIRE. ELECTRICAL FITTINGS ARE LOOSE AT CONNECTION TO DISCONNECT A/C UNIT. 2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. 3) INSTALL A GAS SHUT OFF VALVE AT GAS LINE CONNECTION IN CLOSET & TEST NEW GAS PIPE MIN 10 LB TEST. RECALL FOR INSPECTION. |