Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/07/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. | |
| 02/28/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1.) PROVIDE A CONDENSATE DRAIN TRAP. 2.) SINGLE WALL VENT CONNECTOR MUST BE MIN 6" FROM COMBUSTIBLES. 3.) A BUSHING IS REQUIRED WHERE WIRES PENETRATE THE ELEC. DISCONNECT. 4.) CONDENSOR IS OVERFUSED AT 45AMP 40AMP IS MAX. |