Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORECTIONS HAVE BEEN MADE. | |
| 02/13/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*1.) VENT FROM FURANCE IS LOOSE & NOT FASTENED TO FLUE PIPE ADEQUATELY. SINGLE WALL VENT PIPE NEEDS MIN 6" CLEARANCE FROM PVC PIPE OR USE DOUBLE WALL PIPE. 2.) TIGHTEN ROMEX CONNECTOR RECALL FOR INSPECTION. |