Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03ME00057
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE. | |
| 04/03/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*A TRAP IS REQUIRED ON ALL DRAIN PANS THAT ARE INTERNAL TO THE EQUIPMENT. PROVIDE A TRAP & RECALL FOR INSPECTION. | |
| 03/27/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* PROVIDE A TRAP ON CONDENSATE DRAIN LINE. REFRIGERATION LINE IS SCRAPIN ON CABINET OF COIL. PROVIDE ISOLATION. CONDENSOR IS FUSED AT 40AMP TO 35AMP IS MAX. FUSE SIZE. RECALL FOR INSPECTION. |