Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/29/2004 |
ELECTRIC - FINAL |
|
Approved |
SENT TO TEP ON 01/30/04AM |
| 12/31/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) GROUND RODS REQUIRED BY NEC TO BE FLUSH TO GRADE. 2) #4 BARE COPPER TO BE SECURED TO WALL WHERE NOT TIED TO PIPE. 3) 3" STEP UP BELOW SERVICE - AT LEAST 1/3 INTO PANEL SPACE - FLOOR BELOW SERVICE TO BE EVEN AS TO NOT CAUSE TRIP HAZARD. NEED TO EVEN OUT SPACE ON FLOOR BELOW. CORRECT AND RECALL. / TEP DROP OVER ROOF SUBJECT TO TEP. |