Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/26/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/25/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ SET APPOINTMENT FOR 9:30. 9:50, NO ONE HERE. |
| 03/22/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) CALLED TOM TO UNLOCK-NO ANSWER, LEFT MESSAGE. REFEE NEXT REQUEST |
| 03/17/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ OK TO CLEAR UPGRADE. CALL FOR FINAL ONCE SHOP SUB PANEL CAN BE INSPECTED. LOCKED TODAY NO ONE HOME. |
| 12/31/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEC REQUIRES CLEARANCE BELOW ALL ELECTRICAL PANELS - GAS LINE AND IRRIGATION LINES ARE RIGHT BELOW PANEL AND WATER. 2) GFI RECEPTACLE BELOW PANEL CANNOT BE SOLEY SUPPORTED BY CHASE NIPPLE. 3) FEEDER TO SHOP SUB PANEL NOT TERMINATED. |