Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL02440

Parcel: 131071290


Addresses:

6202 E 26TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/31/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) NEED 2 GROUND RODS 6' APART, CLAMPS NEED TO BE BRASS, DRIVE GROUND RODS TO GRADE. 2) ADDRESS SERVICE PERMANENTLY. 3) RISER ABOVE ROOF NEEDS KICKER OR GUY BACK.
12/31/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ RE-INSPECTED IN PM - CORRECTIONS MADE.