Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/18/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK TO CLEAR 2) WILL NOTIFY TEP 3) TEP CONDUCTORS SUBJECT TO TEP .SENT TO TEP ON 12/19/03AM |
| 12/16/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) MAINTAIN CLEARANCE OF SERVICE CONDUCTORS ABOVE SPA PER 680.8. PLEASE VERIFY TEP CLEARANCE 2) JUNCTION BOX IS NEEDED-CANNOT USE OLD DISCONNECT AS JUNCTION BOX 3) CANNOT USE SHEET METAL SCREW FOR GROUNDING 250.8 4) PLEASE CLEAN SURFACE UNDER LUG 250.12 5) CORRECTLY IDENTIFY GROUNDING EQUIPMENT CONDUCTOR 250.19 6) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTOR 7) RISER SCREWS TO BE 1/4" MINIMUM 8) TIGHTEN LOOSE FITTINGS 9) FINISH DRIVING 1ST GROUND ROD |