Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/05/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 03/08/04AM |
| 01/23/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ TERMINATE ALL GROUNDS AND NEUTRALS IN MAIN GROUND BAR AREA. MUST HAVE A PERMANENT METAL ADDRESS TAG SCREWED OR RIVITED INTO BOX. ID CIRCUITS. BOND GAS PIPING SYSTEM. EXPOSE GROUNDWORK. IS WATER BOND CONTINUOUS FROM SERVICE TO WATER? |