Permit: T03EL02396

Parcel: 121063820


Addresses:

5722 E BELLEVUE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/16/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ OK TO CLEAR
12/12/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) CODE REQUIRES SCH. 80 PVC ABOVE GROUND WHEN EXPOSED, [AT RISER TO HOUSE PANEL] 2) SAME AS #1 ON MAIN SERVICE, SCH 80 PVC REQUIRED ABOVE GROUND. 3) MAIN SERVICE REQUIRES A MIN. OF 36" IN FRONT OF SERVICE, ONLY HAVE 32" - PLEASE CORRECT AND RECALL.