Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/08/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 03/09/04AM |
| 03/02/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |
| 02/19/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE REQUIRES 2 GROUND RODS. 2) PLEASE SCRAPE PAINT FROM PIPE AT GAS BOND CONNECTION. 3) CANNOT HAVE UTILITY AND PREMISER WIRING IN SAME COMPARTMENT. LOAD WIRE GOING THROUGH ISOLATED DEDICATED AREA. ALSO SEE LISTING. |