Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*/ 1) OK TO CLEAR INCREASE 2) CALL FOR FINAL AFTER TIE-IN | |
| 05/28/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT PVC CONDUIT UNDER PANEL. 2) CHASE NIPPLE NOT ALLOWED FOR FEEDER TERM. USE CLOSE NIPPLE AND BOND BUSHING ON CONCENTRI K.O. 3) PLUG UNUSED OPENING IN J-BOX. |
|
| 05/17/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ NO ANSWER - LOCKED - DOGS - A RE-FEE IS DUE BEFORE NEXT INSP. |
|
| 04/20/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*/ 1) USE RISER CONDUCTORS THAT ARE MARKED OUTDOOR OR SUNLITE RESISTANT. 2) INSTALL BOND BUSHINGS ON ENDS OF CONDUIT WHEN USING STEEL FOR #4 GROUNDING CONDUCTOR. 3) MUST HAVE 2 GROUND RODS 6' MIN. APART. 4) BOND WTR AND GAS PIPING. 5) SUPPORT RISER CONDUIT WITHIN 3' OF PANEL, USE ¼" BOLTS TO SUPPORT. 6) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED. |