Permit: T03EL02355

Parcel: 138231340


Addresses:

641 W ELVIRA RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/09/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*/ 1) OK TO CLEAR INCREASE 2) CALL FOR FINAL AFTER TIE-IN
05/28/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT PVC CONDUIT UNDER PANEL. 2) CHASE NIPPLE NOT ALLOWED FOR FEEDER TERM. USE CLOSE NIPPLE AND BOND BUSHING ON CONCENTRI K.O. 3) PLUG UNUSED OPENING IN J-BOX.
05/17/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ NO ANSWER - LOCKED - DOGS - A RE-FEE IS DUE BEFORE NEXT INSP.
04/20/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*/ 1) USE RISER CONDUCTORS THAT ARE MARKED OUTDOOR OR SUNLITE RESISTANT. 2) INSTALL BOND BUSHINGS ON ENDS OF CONDUIT WHEN USING STEEL FOR #4 GROUNDING CONDUCTOR. 3) MUST HAVE 2 GROUND RODS 6' MIN. APART. 4) BOND WTR AND GAS PIPING. 5) SUPPORT RISER CONDUIT WITHIN 3' OF PANEL, USE ΒΌ" BOLTS TO SUPPORT. 6) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED.