Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*/ 1) OK TO CLEAR INCREASE 2) CALL FOR FINAL AFTER TIE-IN | |
| 05/28/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT PVC CONDUIT UNDER PANEL. 2) CHASE NIPPLE NOT ALLOWED FOR FEEDER TERM. USE CLOSE NIPPLE AND BOND BUSHING ON CONCENTRI K.O. 3) PLUG UNUSED OPENING IN J-BOX. |
|
| 05/17/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ NO ANSWER - LOCKED - DOGS - A RE-FEE IS DUE BEFORE NEXT INSP. |
|
| 04/20/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*/ 1) USE RISER CONDUCTORS THAT ARE MARKED OUTDOOR OR SUNLITE RESISTANT. 2) INSTALL BOND BUSHINGS ON ENDS OF CONDUIT WHEN USING STEEL FOR #4 GROUNDING CONDUCTOR. 3) MUST HAVE 2 GROUND RODS 6' MIN. APART. 4) BOND WTR AND GAS PIPING. 5) SUPPORT RISER CONDUIT WITHIN 3' OF PANEL, USE ΒΌ" BOLTS TO SUPPORT. 6) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED. |