Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/10/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 01/16/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ LAST PART OF NOTE #1 FROM PREVIOUS INSPECTION NOT FINISHED. |
| 01/08/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TO CLEAR SERVICE UPGRADE 2) OK INSIDE- CALL BACK FOR FINAL ONCE EVERYTHING FINISHED. ROMEX BEHIND WASHER STILL WILL NEED PHYSICAL PROTECTION |
| 01/07/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) WITH RISER EXTENDING 3" ABOVE ROOF, 2" RISER NEEDS A GUY BACK SUPPORT OR A KITCHEN SUPPORT 2) J-BOX IN WASH ROOM MUST BE GROUNDED 3) CANNOT HAVE EXPOSED ROMEX BELOW 8' UNPROTECTED ALSO ROMEX COMING INTO A METAL J-BOX MUST BE CLAMPED TO BOX-BUSHING OF PLASTIC, NOT ALLOWED 4) THIS PERMIT IS FOR UPGRADE ONLY CANNOT APPROVE ANY NEW INSIDE WIRING WITH OUT ADDITIONAL PERMIT FOR NEW CIRCUITS, DRYER, TWO KITCHEN CIRCUITS, NEW WIRING FOR BACK ROOM LIGHT 5) WASHROOM J-BOX AT CEILING BY WATER HEATER. PUSH CONDUCTORS BACK INTO BOX TO OPEN COVER FREELY. ADD EXTENSION RING |