Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL02308
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
12/03/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) 2 - GROUND RODS REQUIRED, PER ART 250 NEC. 6' MIN APART. 2) EXPOSE UNDERGROUND FOR INSP. 3) BOND GAS PIPING FOR BOTH METERS. |