Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/09/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 12/10/03AM |
| 11/25/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) MAINTAIN WORKING CLEARANCES 110.26 2) CLEAN SURFACES FOR BOND CLAMPS 3) COVER TO BE WEATHER PROOF WHEN PLUGED-IN 410.57 4) SUPPORT CONDUITS ABOVE PANEL 5) ENTRANCES ABOVE CURRENT CARRING PARTS TO BE SEALED 6) TIGHTEN LOOSE FITTINGS 7) JUNCTION BOX OVER FILLED FOR CONDUCTORS-ALSO BLUE WIRE NUTS ONLY LISTED FOR 2-#8 NO LARGER. GROUND JUNCTION BOX 8) PLEASE CLEAN OIL SUBSTANCE OUT OF BOTTOM OF PANEL 9) TIGHTEN LOOSE TERMINATIONS |