Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2 1/2" PLASTIC BUSHING USED MUST BE A GROUNDING TYPE WITH A LUG AND A JUMPER TO ENCLOSURE (GOING THRU A CONCENTRATION KO) 2) GROUND RODS TO BE DRIVEN STRAIGHT DOWN: 1ST METHOD ST DOWN 2ND METHOD 45 DEGREE IF ROCK ENCOUNTERED 3RD METHOD 90 DEGREE FLAT UNDER 2 1'2 DIRT IF ROCK ENCOUNTERED. |
|
| 05/10/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* |