Permit: T03EL02286

Parcel: 124032450


Addresses:

1716 E 7TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T03EL02286

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*SENT TO TEP ON 02/10/04AM
01/02/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0215*/ CORRECTIONS REQUIRES: 1) PUT PERMANENT ADDRESS ON PANEL ABOVE METER. USE PERMANENT LETTERS AND NUMBERS. USE METAL STRIP. DO NOT USE PEN, PENCIL OR MAGIC MARKER. 2) COMPLETE THE DIRECTORY. MARK ALL CIRCUITS. 3) ADD STRAP TO RISER CONDUIT - WITHIN 8" OF TOP OF PANEL. 4) WHERE IS WATER PIPE GROUND BOND? 5) PROVIDE COPY OF PERMIT FOR INSTALLATION OF ROOF MTD. A/C - HEATER. 6) PROVIDE COPY OF PERMIT FOR GAS PIPING. I SUGGEST YOU OBTAIN A GENERAL REPAIRS PERMIT.
11/27/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*