Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T03EL02286
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/09/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*SENT TO TEP ON 02/10/04AM | |
01/02/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0215*/ CORRECTIONS REQUIRES: 1) PUT PERMANENT ADDRESS ON PANEL ABOVE METER. USE PERMANENT LETTERS AND NUMBERS. USE METAL STRIP. DO NOT USE PEN, PENCIL OR MAGIC MARKER. 2) COMPLETE THE DIRECTORY. MARK ALL CIRCUITS. 3) ADD STRAP TO RISER CONDUIT - WITHIN 8" OF TOP OF PANEL. 4) WHERE IS WATER PIPE GROUND BOND? 5) PROVIDE COPY OF PERMIT FOR INSTALLATION OF ROOF MTD. A/C - HEATER. 6) PROVIDE COPY OF PERMIT FOR GAS PIPING. I SUGGEST YOU OBTAIN A GENERAL REPAIRS PERMIT. | |
11/27/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* |