Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/09/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 02/10/04AM |
| 01/02/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0215*/ CORRECTIONS REQUIRES: 1) PUT PERMANENT ADDRESS ON PANEL ABOVE METER. USE PERMANENT LETTERS AND NUMBERS. USE METAL STRIP. DO NOT USE PEN, PENCIL OR MAGIC MARKER. 2) COMPLETE THE DIRECTORY. MARK ALL CIRCUITS. 3) ADD STRAP TO RISER CONDUIT - WITHIN 8" OF TOP OF PANEL. 4) WHERE IS WATER PIPE GROUND BOND? 5) PROVIDE COPY OF PERMIT FOR INSTALLATION OF ROOF MTD. A/C - HEATER. 6) PROVIDE COPY OF PERMIT FOR GAS PIPING. I SUGGEST YOU OBTAIN A GENERAL REPAIRS PERMIT. |
| 11/27/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |