Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/01/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* SENT TO TEP ON 03/02/04AM |
| 02/23/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) INSTALL BOND BUSHING WHERE USING CONCENTRIC KO'S. 2) USE CLOSE NIPPLE INSTEAD OF CHASE NIPPLE AT BOTTOM OF PANEL. OR LOCK NUT BOTH INSIDE AND OUT. 3) OLD FPE SUB-PANEL NOT LISTED AS USE FOR J-BOX, USE APPROVED J-BOX. 4) EXPOSE GROUND RODS FOR INSP. 5) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED. 6) BOND GAS PIPING. |