Permit: T03EL02282

Parcel: 138141770

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/01/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000* SENT TO TEP ON 03/02/04AM
02/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) INSTALL BOND BUSHING WHERE USING CONCENTRIC KO'S. 2) USE CLOSE NIPPLE INSTEAD OF CHASE NIPPLE AT BOTTOM OF PANEL. OR LOCK NUT BOTH INSIDE AND OUT. 3) OLD FPE SUB-PANEL NOT LISTED AS USE FOR J-BOX, USE APPROVED J-BOX. 4) EXPOSE GROUND RODS FOR INSP. 5) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED. 6) BOND GAS PIPING.