Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL02273
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ A VIOLATION OF CITY ORDINANCE STILL EXISTS, PERTAINING TO THE NATIONAL ELEC. CODE. THE CLEARANCE IN FRONT OF THE CIRCUIT BREAKER PANEL BOARD MUST BE A MIN. OF 3 FT OUT PERPENDICULAR FROM M.H. UNIT. PLEASE TAKE CARE OF THIS WITHIN 3 DAYS. A FOLLOW UP WILL BE MADE. | |
11/21/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ WILL CALL POWER CLEARANCE. A VIOLATION OF THE NEC. EXISTS WHICH IS HAVING PROPER WORKING CLEARANCES IN FRONT OF THE CIRCUIT BREAKER BOX. THE SHED MUST BE MOVED OUT SO THAT THERE WILL BE A MIN. OF 3' BETWEEN BOX AND SHED. A FOLLOW UP WILL BE MADE IN 3 WEEKS. |