Permit: T03EL02261

Parcel: 107081360


Addresses:

831 W TIPTON DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL02261

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ CORRECTIONS REQUIRED: 1) INSTALL A PERMANENT METALLIC ADDRESS TAG ON THE NEW SERVICE PANEL. PLACE ABOVE OR BELOW METER. 2) COMPLETE THE CIRCUIT DIRECTORY. 3) GUTTED OUT DISCONNECT ENCLOSURES [CAN] ARE NOT LISTED FOR USE AS JUNCTION BOXES. 4) THE BUNDLING OF THE GROUND WIRES WITH THE TY-RAYS IS NOT SUFFICIENT SUPPORT. ADD MIN. OF TWO STRAPS ANCHORED TO BRICK WALL.