Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/05/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/04/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ CORRECTIONS REQUIRED: 1) INSTALL A PERMANENT METALLIC ADDRESS TAG ON THE NEW SERVICE PANEL. PLACE ABOVE OR BELOW METER. 2) COMPLETE THE CIRCUIT DIRECTORY. 3) GUTTED OUT DISCONNECT ENCLOSURES [CAN] ARE NOT LISTED FOR USE AS JUNCTION BOXES. 4) THE BUNDLING OF THE GROUND WIRES WITH THE TY-RAYS IS NOT SUFFICIENT SUPPORT. ADD MIN. OF TWO STRAPS ANCHORED TO BRICK WALL. |