Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/03/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* OK TO CLEAR 1,2 SENT TO TEP ON 12/03AM |
| 11/20/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*/ NOTES: GROUND BAR MUST BE ISOLATED FROM GROUND AS PER LAST WRITE UP. REMOVE #4 BOND JUMPER FROM NEUTRAL BAR TO GROUND LUG ON ENCLOSURE. ART. 250-32. A RE-INSPECTION FEE IS ASSESSED, PAY RE-FEE AT 201 N STONE PRIOR TO NEXT INSP. |
| 11/18/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) STRAP #4 BARE WIRE TO STRUCTURE BOTH UNITS 2) SEPERATE GROUNDS AND NEUTRALS AT SUB-PANEL FOR UNIT #1 250.32 NEC |
| 11/06/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) NOTES: #9 RISER CONDUCTORS MUST BE MARKED BY MANUFACTURER OF TYPE AND SIZE PER NEC 2) NEED TO VERIFY WATER AND GAS BONDING 3) PVC CONDUIT MUST BE SCHEDULE 80 PER #9287 CITY OF TUCSON ORDINANCE ALSO NOT SUPPORTED 4) ID CIRCUIT BREAKERS IN SUB-PANELS 5) MUST HAVE OWN GROUNDING ELECTRODE SYSTEM AT UNIT #1 PER 250 NEX 250.32 6) MAIN BREAKER MUST HAVE A DEVICE THAT IS LISTED TO SECURE BREAKER TO BUSS 7) CIRCUIT BREAKERS MUST BE OF SAME MANUFACTURER AS PANEL BOTH UNITS 8) USE LISTED ICO PLUG FOR SUB-PANEL AT UNIT #2 FOR SIDE. MUST BE OUTDOOR RATED |