Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/10/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
SENT TO TEP ON 1112AM |
| 11/05/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) INSTALL PERMANENT ADDRESS LABEL, MUST BE SCREWED OR RIVITED TO ENCLOSURE 2) CHASE NIPPLE 1 1/2" MUST HAVE LOCKNUT OR USE CLOSE NIPPLE WITH LOCKNUTS BOTH SIDES AND BOND BUSHING, WHEN USING CONCENTRIC, KO'S 3) ID CIRCUIT BREAKERS 4) 2 GROUND RODS REQUIRED 6' APART MINIMUM GROUNDING WIRE MUST BE UNSPLICED 5) BOND GAS AND WATER PIPES |