Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/21/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 01/22/04AM |
| 12/30/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245* |
| 12/09/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) IN ORDER TO HAVE A 200 AMP SERVICE THE RISER WIRES HAVE TO BE AT LEAST 2/0 COPPER 2) THE METER BASE AND WIRING HAVE TO BE RATED 200 AMP 3) BE BONDED TOGETHER, ALSO SUPPORT TO WALL UNDER SERVICE 4) THE SERVICE HAS TO HAVE THE STREET ADDRESS ON IT PERMANENTLY MARKED, NO MARKER 5) PLASTIC PVC CONDUIT CANNOT BE USED OUSIDE UNLESS SCHEDULE 80 TYPE-HEAVY DUTY 6) PANEL SCHEDULE NEEDS TO BE FILLED OUT 7) ON A NEW 200 AMP SERVICE THE RISER HAS TO HAVE A SUPPORT BELLOW AND ABOVE ROOF |