Permit: T03EL02173

Parcel: 130071040


Addresses:

3755 E JUAREZ ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/21/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*SENT TO TEP ON 01/22/04AM
12/30/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
12/09/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) IN ORDER TO HAVE A 200 AMP SERVICE THE RISER WIRES HAVE TO BE AT LEAST 2/0 COPPER 2) THE METER BASE AND WIRING HAVE TO BE RATED 200 AMP 3) BE BONDED TOGETHER, ALSO SUPPORT TO WALL UNDER SERVICE 4) THE SERVICE HAS TO HAVE THE STREET ADDRESS ON IT PERMANENTLY MARKED, NO MARKER 5) PLASTIC PVC CONDUIT CANNOT BE USED OUSIDE UNLESS SCHEDULE 80 TYPE-HEAVY DUTY 6) PANEL SCHEDULE NEEDS TO BE FILLED OUT 7) ON A NEW 200 AMP SERVICE THE RISER HAS TO HAVE A SUPPORT BELLOW AND ABOVE ROOF