Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ CORRECTIONS COMPLETED. |
| 11/12/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) SEPARATE GROUNDING EQUIPMENT CONDUCTORS TO PANEL WHERE CIRCUIT ORIGINATES. GROUNDING EQUIP CONDUCTORS NOT TO BE WHITE. 2) PLEASE FINISH #3 OF PREVIIOUS INSP. #12 UNDER MOUNTING SCREW NOT CORRECT |
| 11/05/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PLEASE VERIFY GAS BONDS ALL UNITS 2) FILL UNUSED OPENINGS BOXES AND PANELS 3) JUNCTION BOX BONDING JUMPER TO BE SIZED PER LARGEST OVER CURRENT DEVICE AND TABLE 250.122 6) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 7) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 8) PROPERLY SUPPORT CONDUIT AND USE CORRECT SIZED STRAPS |