Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 12/03/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0920*/ LOCKED NO ENTRY - DOGS |
| 11/20/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) I.D. BLACK CONDUCTOR GOING INTO NEUTRAL BAR WHITE. 2) BROKEN CONNECTOR AT ½" LB NOT APPROVED, USE CLOSE NIPPLE WITH SEALING LOCKNUTS, SUPPORT ½" CONDUIT PER CODE. 3) ADDRESS LABEL NEEDS TO BE ATTACHED BY SCREWS OR RIVITS. |