Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/20/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 11/06/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*SENT TO TEP ON 1107AM |
| 11/04/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ NOTES: 1) NEED TO VERIFY WATER AND GAS PIPE BONDS. 2) BOND BUSHINGS REQUIRED IN GUTTER WHEN USING NIPPLES. BOND TO GROUND SYSTEM. 3) BOND BUSHING REQUIRED WHEN USING METAL CONDUIT AS SLEEVE FOR GROUNDING ELECTRODE CONDUCTOR, REMOVE NIPPLE BETWEEN SERVICE PANELS TO PREVENT POSSIBLE INTER-CONNECTION OF CONDUCTORS. SEE ART 250 OF NEC. |