Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/30/2003 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000* SENT TO TEP ON 103103AM
10/28/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) SINCE HOUSE IS VACANT, SERVICE UPGRADE REQUIRED TO BE INSTALLED BY A LICENSED CONTRACTOR. PLEASE PROVIDE NAME AND LETTER OF RESPONSIBILITY. TO MANY ITEMS WRONG. 1) ADDRESS ON SERVICE, NO MARKER. 2) GROUNDING SYSTEM 3) WRONG TYPE 30A CB IN SERVICE 4) RECEPTACLE BELOW SERVICE TO BE GFCI 5) INSUFFICENT TAPING ON EXISTING CONDUCTOR IN J-BOX 6) GROUND J-BXOES 7) WHAT IS NEW CIRCUIT FOR (1/2" CONDUIT FROM SERVICE) 8) OPEN CB SPACES IN PANEL AREA 9) INSIDE DRYER AIR IMPROPERLY INSTALLED UNLESS A LICENSED ELECTRICIAN DOING CHANGE OVER. HAVE TEMP FEED REMOVED ASAP