Permit: T03EL02101

Parcel: 128114200


Addresses:

4936 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03EL02101

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/24/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 1125AM
11/17/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ A REFEE IS DUE BEFORE THE NEXT INSPECTION. - PLEASE COMPLETE ITEMS 1 & 2 FROM PREVIOUS INSP. SEE ADDRESS ON THIS PERMIT.
10/30/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) THIS SPACE IS REQUIRED TO HAVE AN ADDRESS VISIBLE FROM THE STREET JUST AS NEXT DOOR '4934' POSTED ON BLDG. 2) THE ELECTRICAL SERVICE MUST HAVE A PERMANENT ADDRESS ON IT. 3) FIXTURE IN BACK ROOM HAS AN EXTENSION CORD COMING OUT OF IT WHICH NEEDS TO BE REMOVED. 4) PANEL IN BATHROOM ALL #12 GROUND WIRES ARE TERMINATED UNDER ONE LARGE LUG WHICH IS HELD DOWN BY A SHEET METAL SCREW. THIS IS AN IMPROPER AND DANGEROUS GROUND TIE. MUST INSTALL A GROUND BAR AND TIE EACH GROUND SEPERATLY. 5) CEILING FANS IN OFFICE ARE TIED TO EXISTING FIXTURES WITH SPEAKER WIRES AND EXPOSED CONDUCTORS. REMOVE OR CORRECT. 6) CEILING LIGHT IN HALL TIED INTO FIXTURES IN OFFICE TO BE REMOVED OR CORRECTED.