Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03EL02101
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/24/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1125AM | |
11/17/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ A REFEE IS DUE BEFORE THE NEXT INSPECTION. - PLEASE COMPLETE ITEMS 1 & 2 FROM PREVIOUS INSP. SEE ADDRESS ON THIS PERMIT. | |
10/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) THIS SPACE IS REQUIRED TO HAVE AN ADDRESS VISIBLE FROM THE STREET JUST AS NEXT DOOR '4934' POSTED ON BLDG. 2) THE ELECTRICAL SERVICE MUST HAVE A PERMANENT ADDRESS ON IT. 3) FIXTURE IN BACK ROOM HAS AN EXTENSION CORD COMING OUT OF IT WHICH NEEDS TO BE REMOVED. 4) PANEL IN BATHROOM ALL #12 GROUND WIRES ARE TERMINATED UNDER ONE LARGE LUG WHICH IS HELD DOWN BY A SHEET METAL SCREW. THIS IS AN IMPROPER AND DANGEROUS GROUND TIE. MUST INSTALL A GROUND BAR AND TIE EACH GROUND SEPERATLY. 5) CEILING FANS IN OFFICE ARE TIED TO EXISTING FIXTURES WITH SPEAKER WIRES AND EXPOSED CONDUCTORS. REMOVE OR CORRECT. 6) CEILING LIGHT IN HALL TIED INTO FIXTURES IN OFFICE TO BE REMOVED OR CORRECTED. |