Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/17/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 12/18/03AM |
| 12/02/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) 2 GROUND RODREQUIRED ON NEW 400A. SERVICE 6' MIN. APART. 2) PROVIDE APPROVED PLANS FOR SERVICE AND ALL NEW WIRING, DEVICES, EQUIP. FOR ALL THREE UNITS. 3) STRAP #4 BARE TO WALL BY SERVICE. 4) SUPPORT CONDUIT ON ROOF AT 10' INTERVALS AND WITHIN 3' OF TERMINATION PER NEZ. |