Permit: T03EL02096

Parcel: 129132880


Addresses:

707 E 35TH ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/17/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 12/18/03AM
12/02/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) 2 GROUND RODREQUIRED ON NEW 400A. SERVICE 6' MIN. APART. 2) PROVIDE APPROVED PLANS FOR SERVICE AND ALL NEW WIRING, DEVICES, EQUIP. FOR ALL THREE UNITS. 3) STRAP #4 BARE TO WALL BY SERVICE. 4) SUPPORT CONDUIT ON ROOF AT 10' INTERVALS AND WITHIN 3' OF TERMINATION PER NEZ.