Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/06/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 1107AM |
| 11/04/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) FINISH PREVIOUS LIST |
| 10/27/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) INTERIOR GAS TO BE BONDED 2) SUPPORT CONDUITS AS PER CODE 3) WE HAVE LOOSE WIRE TERMINATION 4) LABEL BREAKERS 5) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS 6) GROUND JUNCTION BOX ENCLOSURE 7) BLUE WIRE NUTS NOT LISTED FOR THIS SIZE CONDUCTORS 8) GROUNDING EQUIPMENT CONDUCTOR TO BE COLOR ENTIRE LENGTH 9) TIGHTEN LOOSE FITTINGS 10) USE CORRECT SIZED STRAPS FOR RISER |