Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL02076

Parcel: 11106246D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/06/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 1107AM
11/04/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) FINISH PREVIOUS LIST
10/27/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) INTERIOR GAS TO BE BONDED 2) SUPPORT CONDUITS AS PER CODE 3) WE HAVE LOOSE WIRE TERMINATION 4) LABEL BREAKERS 5) GROUNDING ELECTRODE CONDUCTOR TO BE CONTINOUS 6) GROUND JUNCTION BOX ENCLOSURE 7) BLUE WIRE NUTS NOT LISTED FOR THIS SIZE CONDUCTORS 8) GROUNDING EQUIPMENT CONDUCTOR TO BE COLOR ENTIRE LENGTH 9) TIGHTEN LOOSE FITTINGS 10) USE CORRECT SIZED STRAPS FOR RISER