Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
1) OK FINAL AND OK TO CLEAR |
| 11/19/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 11/04/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) CLEAN SURFACE UNDER LUG 250.12 2) TIGHTEN LOOSE CONDUCTOR TERMINATIONS 3) WHERE IS RUBBER TAPE FOR SPLICE-SPLICES TO BE EQUAL TO ORIGINAL INSULATION 110.14 4) WE HAVE MULITPLE TERMINATIONS OF NEW CONDUCTORS AT DISCONNECT 5) NEUTRAL-GROUNDING CONDUCTORS TO BE IDENTIFIED AS PER 200.6 6) HIGH LEG TO BE IDENTIFIED AT WEATHER HEAD 7) FINISH ITEMS #2, 3, 6 AND 8 OF PREVIOUS INSPECTION |
| 10/27/2003 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2) MAINTAIN WORKING CLEARANCES AT NEW ELECTRICAL EQUIPMENT 110.26 3) WATER BONDING IS NEEDED 250.104 4) LABEL BREAKERS 5) TRIMING OF CONDUCTOR NOT ALLOWED 6) BONDING DEVICES NEED AT SERVICE NIPPLE 250.94 7) WE HAVE MULTIPULE TERMINATIONS AT GROUNDED CONDUCTOR 8) POWER LEG TO BE CORRECTLY IDENTIFIED AND PANEL TO BE LABELED 9) JUNCTION BOX TO BE BONDED 250.148 10) GROUNDING EQUIPMENT CONDUCTOR TO BE COLORED ENTIRE LENGTH 250.119 11) BLE WIRE NUTS NOT LISTED FOR CONDUCTORS OF THIS SIZE 110.3 12) TIGHTEN LOOSE FITTINGS 13) BREAKER TO BE LISTED FOR USE BY MANUFACTURER 14) FINISH ALL CIRCUIT CONNECTION OR REMOVE 15) THIS IS A SERVICE UPGRADE |